§ 39-89. Irrigation plan requirements.  


Latest version.
  • (a)

    All multifamily and nonresidential uses shall require an irrigation plan which shall include the following:

    (1)

    A minimum scale of one (1) inch to twenty (20) feet;

    (2)

    The location of all surveyed existing and proposed trees, vegetation, or ecological communities to be preserved, as required and approved by the EPGMD (See Section 39-80);

    (3)

    The location and outline of existing and proposed buildings and site improvements, water bodies, and hardscape features such as driveways, sidewalks, pools, fountains, fences, and retaining walls;

    (4)

    The location of all on grade, underground, and overhead utilities;

    (5)

    The location of the nearest recycled or reuse water main within one thousand (1,000) feet of the nonresidential subject property;

    (6)

    The irrigation POCs, the design capacity, and the water service pressure at irrigation POCs;

    (7)

    The water meter size;

    (8)

    The major components and location of the irrigation system, including all pumps, filters, valves, and pipe sizes and lengths;

    (9)

    Reduced-pressure-principle backflow-prevention devices for each irrigation POC on potable water systems and specifications;

    (10)

    The locations and specifications of controllers of rain shut-off devices and soil moisture sensors;

    (11)

    A notation indicating that all landscape areas shall be provided with an automatically operating, underground irrigation system designed to have head-to-head coverage (one hundred percent (100%) coverage with one hundred percent (100%) overlap);

    (12)

    An irrigation legend with the following elements:

    a.

    Separate symbols for all irrigation equipment with different spray patterns, precipitation rates, and pressure compensating devices;

    b.

    General description of equipment, including the manufacturer's name and model number for all specified equipment;

    c.

    Recommended operating pressure per nozzle, bubbler, and low flow emitter;

    d.

    Manufacturer's recommended overhead and bubbler irrigation nozzle rating in gallons per minute, or gallons per hour for low flow point applicators;

    e.

    Minimum (no less than seventy-five percent (75%) of maximum spray radius) and maximum spray radius per nozzle; and

    f.

    Manufacturer's rated precipitation rate per nozzle at specified pounds per square inch (psi); and

    (13)

    Zone layout plan (minimum scale of one (1) inch to twenty (20) feet):

    a.

    Indicating head type, specifications, and spacing; and

    b.

    Indicating methods used to achieve compliance with landscape irrigation design standards, as required by Section 373.228, Florida Statutes.

(Ord. No. 2017-15 , § 18, 5-23-17)